Welcome to Anhui Gaosheng Electric Group Co., Ltd.!
+0086 15212195160(Manager)
Enter product keywords

Single Flange Pressure Transmitter

product details

Products

Single Flange Differential Pressure Transmitter adopts fully sealed welded structure Diversified shape structure, high temperature resistant circuit board Sensor anti-interference, good long-term stability, lightning protection, anti-frequency interference, high precision, high stability, 316 stainless steel isolation diaphragm structure (or tantalum diaphragm), a variety of ranges to choose from, the user is convenient for debugging.

Functions of single-flange pressure transmitter

Output: 2-wire, 4~20mA DC output, digital communication, programmable set linear or square root output mode, HART protocol loaded on 4~20mA DC signal.

Power supply voltage: working condition: 10.5~42V DC

Digital communication: 16.4~42V DC

Intrinsically safe: 16.4~30V DC

Load (when output signal code is D and E): Operating status: 0 to 1335Ω Digital communication: 250 to 600Ω

HART Communication Distance: The communication distance can be up to 2Km with multi-core twisted pair cable, and the communication distance varies depending on the cable type. The formula is as follows: L=65000000/(R×C)-(C1+10000)/C

L=Length (m and ft)

R=impedance (Ω , including power supply impedance)

C = cable capacitance (pF/m or pF/ft)

C1=maximum parallel capacitance (pF/m or pF/ft)

Damping time constant of monoflange pressure transmitter: the sum of damping time constant of amplifier parts and membrane box. The constant is adjustable in the range of 0.2 to 64 seconds.

Ambient temperature: -40~85℃ (-40~185?F) -30~80℃ (-22~176?F) [with LCD meter head].

Receiving temperature: -40~120℃ (-40~248?F)

Reference accuracy of adjustable range (including linearity, hysteresis and repeatability from zero point): ±0.1 %

Stability of single-flange pressure transmitter: ± 0.1% upper limit of range / 12 months

Performance and parameters:

Output signal: 4 ~ 20MA.DC two-wire (analog)

Two-wire 4 ~ 20mA DC signal superimposed on the digital signal, selected by the user linear or open-square output. (Intelligent)

Power supply: 12~45V.DC

Range ratio: 10:1 or 100 to 1

Power supply influence: <0.005% output range/V

Load effect: No load effect when power supply is stable.

Measurement accuracy: ±0.1% of the tuning range, ±0.2 (standard accuracy is ±0.2%, if you choose other accuracy, please specify when ordering selection.)

Damping: Usually adjustable between 0.1~16 seconds, when filling inert liquid or with remote transmission device, the time constant will increase.

Start-up time: <2 seconds, no warm-up required.

Operating environment: Ambient temperature -29 to 93°C (analog amplifier)

-29~75℃ (digital/intelligent amplifier)

-29~65℃ (with display meter head)

Ambient humidity 0 to 95% (digital/smart amplifier)

Protection characteristics: Protection capability IP65

Explosion-proof type: Explosion-proof type Exd II BT4-6

Intrinsically safe type Exia II CT5

Static pressure effect: DP class zero error: for 14MPa, ±0.1% of the maximum range limit or ±0.25% of the maximum range limit (range code 3), in the pipeline pressure by zeroing to give a correction.

HP class zero error: ±0.5% of the maximum range limit, for 32MPa in the pipeline pressure by zeroing to give a correction.

Electromagnetic radiation effect: 0.05% of the maximum range value, accept radiation frequency 27 ~ 500MHz, test field strength 3V/m.

Indication table (%): LCD digital display Accuracy ±0.2

Vibration effect: any direction 200Hz vibration, ± 0.05% / g.

Installation position: diaphragm is not installed vertically, may produce less than 0.24KPa zero error, but can be corrected by zeroing.

Weight: 3.9Kg (excluding accessories)


product details

Filling in your phone and email information will help us to contact you in a timely manner and solve the problem you raised as soon as possible.

project case
gaosheng electrical