I: Product characteristics and use
This product has the characteristics of cold-resistant, soft, wear-resistant, oil-proof, etc. It is suitable for connecting cables for mobile electric appliances with the rated AC voltage of 0.6/1KV and below with the special requirements of cold-resistant, oil-proof, etc. At present, this product has been widely used in metallurgy, electric power, shipbuilding, automobile manufacturing and other industries.
Second: Product implementation standards
Q/HHTZH007.1
Flame-retardant performance test GB12666-90 regulations
Third: the use of characteristics
>1.AC rated voltage: U0/U 0.6/1KV
Maximum working temperature: 70℃, 90℃, 105℃, 120℃ (according to customer requirements)
Minimum ambient temperature: -42.5℃ for fixed laying
>2. Cable installation and laying temperature should not be lower than -25℃.
>3. Allowable bending radius of cable: cable minimum 12 times the outer diameter of the cable
IV: Basic model and name
Table 1
model number |
Pseudolaric acid |
>YVFR |
Nitrile insulated and sheathed power flexible cables |
>YVFRP |
Nitrile insulated and sheathed copper braided shielded power flexible cable |
Remarks: Add ZR in front of the model number of flame retardant cable, and the copper wire in the conductor core can be tin-plated P1. |
V: Designations and meanings of codes
Table 2
nicknames |
Code Name Meaning |
>YVF |
Nitrile cable series |
>P |
copper braid shielding |
>R |
多stranded conductor |
VI: Main technical indicators
>1. DC resistance of finished cable conductor (class R) (in accordance with GB3956) refer to Appendix A, Table 2.
>2. Insulation resistance is not less than 50MΩ/KM at 20℃.
>3. The finished cable will not break through the AC 50HZ3.5KV/5min voltage test.
Note: Our company can according to customer site requirements: R & D customized production of various types and specifications of cable.
Tel: Mr. Chen 18355080606 (micro letter with number)