I: Product characteristics and use
This product is suitable for AC rated voltage 0.6/1KV and below for fixed laying of transmission and distribution lines, power transmission or motor lead wires, high temperature resistance, corrosion resistance, acid and alkali resistance and corrosive gases, waterproof and other characteristics of the high temperature environment, stable electrical performance, high current-carrying capacity, long service life, is widely used in metallurgy, electric power, petrochemical, large-scale construction, automobile manufacturing and other industries.
Second: Product implementation standards
Q/GS09-2015
Flame-retardant and fire-resistant characteristics test GB12666-90 standard
Third: the use of characteristics
1. AC rated voltage: U0/U 0.6/1KV
2. Maximum working temperature: polyperfluoroethylene propylene (F46) insulation does not exceed 200 ℃.
Soluble polytetrafluoroethylene (PFA) insulation does not exceed 260 ℃.
3. Minimum ambient temperature: Fluorine plastic insulation and sheathing
Fixed laying -40℃, non-fixed laying -15℃.
4. cable installation and laying temperature should not be less than 0 ℃ (fluorine plastic, silicone rubber and nitrile sheathed cable not less than -25 ℃).
5. allowable bending radius of the cable: single-core cable minimum 15 times the outer diameter of the cable
Multi-core cable minimum 10 times the outer diameter of the cable
IV: Basic models and names
Table 1
model number
|
Pseudolaric acid
|
Normal operating temperature ℃
|
FF46
|
Fluoroplastic Insulated and Sheathed Power Cables
|
-60-200
|
FF46-22
|
Fluoroplastic Insulated and Sheathed Steel Tape Armored Power Cables
|
-60-200
|
FF46P
|
Copper braided shielded power cables with fluoroplastic insulation and jacket
|
-60-200
|
ZR-F46(FV)
|
Fluoroplastic Insulated Flame Retardant PVC Sheathed Power Cable
|
-40-105
|
ZR-F46-22(FV22)
|
Fluoroplastic Insulated Steel Tape Armored Flame Retardant PVC Sheathed Power Cable
|
-40-105
|
ZR192-FF46
|
PFA insulated and sheathed power cables (imported raw materials)
|
-60-260
|
ZR192-FF46P
|
PFA insulated and sheathed copper braided and shielded power cables (imported raw materials)
|
-60-260
|
ZR192-FF46-22
|
PFA insulated and sheathed steel tape armored power cables (imported raw materials)
|
-60-260
|
YGC-F46(FG)
|
Fluoroplastic Insulated Silicone Rubber Sheathed Power Cable
|
-60-180
|
YGC-F46-22(FG22)
|
Fluoroplastic Insulated Steel Tape Armored Silicone Rubber Sheathed Power Cable
|
-60-180
|
YVF-F46
|
Fluoroplastic Insulated Flame Retardant Nitrile PVC Sheathed Power Cable
|
-60-105
|
YVF-F46-22
|
Fluoroplastic Insulated Steel Tape Armored Flame Retardant Nitrile PVC Sheathed Power Cable
|
-60-105
|
Remarks: Add R to the prototype number for soft structured cables, and the copper wire in the conductor core can be tinned.
V: Code name and meaning
Table 2
nicknames
|
Code Name Meaning
|
Series Code
|
/
|
F(F46)
|
Polyperfluoroethylene propylene (F46)
|
YVF
|
nitrile rubber
|
G
|
silicone rubber
|
192
|
Imported PFA insulation and jacketing
|
ZR(V)
|
Flame-retardant polyvinyl chloride (flame-retardant 70℃, 90℃, 105℃)
|
22
|
steel strip armor
|
32
|
Fine steel wire armor, 42 thick steel wire armor
|
P
|
Copper braid shielding, P2 copper tape shielding
|
R
|
Multi-stranded conductors
|
VI: Main technical indicators
1. DC resistance of the conductor of the finished cable (in accordance with GB3956) refer to Appendix A, Table 1.
2. 20 ℃ when the insulation resistance is not less than 500MΩ / KM, 180 ℃ when the insulation resistance is not less than 10MΩ / KM
3. The finished cable is subjected to AC 50HZ3.5KV/5min voltage test without breakdown.