1、Use: This product is used for the wiring of electrical appliances and instruments in the power distribution device with AC rated voltage 500V or DC voltage 1000V and below.
2, product use characteristics: the long-term allowable operating temperature of the cable conductor should not exceed 70 ℃. The temperature of the cable should be not less than 0℃ when laying, and the bending radius should be not less than 10 times of the outer diameter of the cable when laying. Cables with armor layer or copper tape shielding structure should be not less than 12 times the outer diameter of the cable.
3、Product standard: GB9330.2-88 “PVC insulated and sheathed control cable”.
4、Cable model, name and scope of use
model number |
Name |
Scope of use |
KVV | PVC insulated, PVC sheathed control cable | Laying indoors, in cable trenches, in conduits and underground. |
KVVP | PVC insulated, PVC sheathed copper wire braid shielded control cable | Laying in the room, cable trench, pipeline and underground, with anti-interference ability |
KVVP | PVC insulated, PVC sheathed flexible control cable | Laying in the indoor movement requirements of soft and other occasions. |
KVVRP | PVC insulated, PVC sheathed copper wire braided shielded flexible control cable | Ditto with anti-jamming capability. |
KVVP2 | PVC insulated, PVC sheathed copper tape wound shielded control cable | Id. |
KVV22 | PVC insulated, PVC sheathed steel tape armored control wires | Laying in the room, cable trench, pipeline and underground, can withstand the use of large mechanical external force. |
KVV32 | PVC insulated, fine steel wire armored PVC sheathed control cable | Laying in indoor, cable trench, pipeline, shaft and underground, can withstand a certain tensile role. |
Note: Flame retardant (ZR) and halogen free flame retardant (ZRA) control cables can be produced according to the needs of users.