ZC-KVV32 4*4 0.45/0.75KV copper core PVC insulated PVC sheathed steel wire armored flame retardant control cable
Characteristics
1) Rated voltage: U0/U is 450/750V.
(2) conductor core long-term operating temperature of 70 ℃, 90 ℃, 105 ℃ three, cable laying temperature of not less than 0 ℃.
(3) The recommended permissible bending radius of the cable is as follows: unarmored cable, should be no less than 6 times the outer diameter of the cable; armored or copper tape shielded cable, should be no less than 12 times the outer diameter of the cable; flexible cable, no less than 6 times the outer diameter of the cable.
● Control cable product description
Execution standard:
GB 9330-88. flame retardant cables should also comply with the technical conditions of IEC332-3 standard.
Explanation
1、Industrial frequency rated voltage Uo/U is 450/750V.
2、The permissible long-term maximum working temperature of the cable conductor is 70℃.
3、The ambient temperature should be not less than 0℃ when the cable is laid, and the cable should be preheated if the ambient temperature is lower than 0℃.
4、The recommended permissible bending radius of the cable is as follows:
5、No armored cable, should be not less than 6 times the outer diameter of the cable;
6, armored or copper tape shielded cable, should be not less than 12 times the outer diameter of the cable;
7. Shielded flexible cable, shall be not less than 6 times the outer diameter of the cable. 8. Fire resistance: NH, steel tape armored: 22, steel wire armored: 32
9. flame retardant grade: ZA (Class A flame retardant), ZB (Class B flame retardant), ZC (Class C flame retardant), ZR (flame retardant)
10. Shielding options: P copper wire, P1 tinned, P2 copper tape, P3 aluminum foil.
11. conductor such as soft structure plus R
ZC-KVV32 Copper core PVC insulated PVC sheathed steel wire armored flame retardant control cable 450/750 2-37
ZC-KYV32 Copper core PVC insulated PVC sheathed steel wire armored flame retardant control cable 450/750 2-37
ZC-KYJV32 Copper-core cross-linked polyethylene insulated PVC sheathed steel wire armored flame retardant control cable 450/750 2-37
KVV22 Copper core PVC insulated PVC sheathed steel tape armored cable 450/750 2-37
0.75-10 Laying in indoor, cable trench, pipeline directly buried and other fixed occasions can withstand large mechanical external force
KVVP22 copper core PVC insulated PVC sheathed steel armored shielded control cable 450/750
2-37 0.75-10 Laying in the room, cable trench, pipeline and other requirements of anti-interference fixed occasions
KVVR22 Copper core PVC insulated PVC sheathed steel armored control flexible cable 450/750
2-37 0.75-10 Laying in the indoor, there are occasions of mobile requirements
KVVRP22 Copper core PVC insulated PVC sheathed steel tape armored braided control flexible cable 450/750 2-37
0.75-10 Laying in the room, there are occasions of mobile requirements
KVVP2-22 Copper core PVC insulated PVC sheathed steel tape armored copper tape shielded control cable 450/750 2-37
0.75-10 Laying in the room, cable trench, pipeline and other requirements of anti-interference fixed occasions
KVVP3-22 Copper core PVC insulated PVC sheathed steel tape armored aluminum-plastic composite tape shielded control cable 450/750
2-37 0.75-10 Laying in indoor, cable trench, pipeline and other requirements of anti-interference fixed occasions
KVVRP2-22 copper core PVC insulated PVC sheathed steel tape armored copper tape shielded control flexible cable
450/750 2-37 0.75-10
Laying in indoor, cable trench, pipeline and other requirements of anti-interference fixed occasions
KVVRP3-22 Copper core PVC insulated PVC sheathed steel tape armored aluminum-plastic composite tape shielded control flexible cable 450/750 2-37
0.75-10 Laying in the room, cable trench, pipeline and other requirements of anti-interference fixed occasions